1GA 50916/CHCO

Wall-mounted carbon monoxide (CO) and natural gas (CH4) detector

The detector can detect two gases: natural gas (CH4) and carbon monoxide (CO)

Intervention sensitivity:
- natural gas at 10% of the lower explosion limit
- carbon monoxide, when the maximum allowed 300ppm CO concentration is exceeded, or rather in case low but damaging concentrations 30ppm for 2 hours persist for long periods in the premises.


TECHNICAL SPECIFICATIONS

Power supply 230V a.c. 50-60Hz

2 potential-free changeover contacts output:
5 (2 )A / 250Va.c.

Natural gas catalytic sensor

Natural gas intervention level 5000 ppm 10% LIE

Semi-conductor sensor for CO

CO intervention level 30 / 300 (30ppm after 2 hours – 300ppm immediately)

Signalling buzzer 85dB at 1m

ON indicator LED

Fault indicator LED

Gas presence indicator LED (2 different)

Protection degree IP 42

Dimensions (L x W x H) 115 x 50 x 150 mm

Need info about this product? Write us